Point Elementary School

Water Testing Results: Point Elementary School

SCI collected 60 drinking water samples from various water fixtures located throughout the structure and submitted them for analytical testing. The water samples were analyzed for lead in accordance with the “Get the Lead Out of School Drinking Water Act,” Section 160.077, which establishes an action level of 5 parts per billion (ppb). The 5 ppb level required by the state is a stricter threshold than the U.S. Environmental Protection Agency’s (EPA’s) recommended action level of 15 ppb.

The drinking water samples that exceeded the state's new action level are identified below.


Published: April 9, 2024
Updated: June 17, 2024

Sample location

Sample description

Result (ppb)

Remediation

Retest Results (ppb)

Kitchen

Double Basin Sink, Right Faucet

6.42

Replaced faucet

1.77

Kitchen

Combi-Oven

15.6

 

 

Kitchen

Handwashing Sink

9.03

Replaced faucet

1

Kitchen

Triple Basin Sink, Left Faucet

9.70

Replaced faucet

<1.0

Library Office

Sink

12.9

Installed new aerator

7.01

Room 24

Sink Faucet

12.5

Installed new stem and aerator

9.09

Room 23

Water Fountain

17.6

Installed new water fountain

7.6

Room 22

Sink Faucet

24.3

Installed new stem and aerator

45.6

Room 22

Sink Spray Nozzle

166

Removed and capped

N/A

Room 21

Sink Faucet

8.69

Replaced faucet

6.51

Room 20

Sink Faucet

14.0

Installed new stem and aerator

6.04

Room 19

Sink Spray Nozzle

722

Removed and capped

N/A

Room 18

Sink Faucet

8.21

Replaced faucet

6.42

Room 15A

Sink Faucet

13.4

Installed new stem and aerator

60.1

Room 14

Sink Faucet

8.22

Replaced faucet

2.23

Room 13

Sink Faucet

7.04

Installed new stem and aerator

2.92

Room 13

Sink Spray Nozzle

13.1

Removed and capped

N/A

Room 12

Sink Faucet

8.49

Replaced faucet

3.74

Room 12

Sink Spray Nozzle

63.1

Removed and capped

N/A

Room 11

Sink Faucet

8.44

Replaced faucet

35.3

Room 10

Sink Faucet

6.71

Replaced faucet

4.06

Room 10

Sink Spray Nozzle

23.6

Removed and capped

N/A

Room 9

Sink Faucet

51.2

Replaced faucet

4.52

Room 9

Sink Spray Nozzle

9.69

Removed and capped

N/A

Room 8

Sink Faucet

10.2

Replaced faucet

1.72

Room 6

Sink Faucet

15.8

Installed new stem and aerator

3.03

On a mobile phone? Turn your phone to landscape.

Notes: Classroom sink spray nozzles are not used for drinking water. Aside from Room 22, the classroom sinks and water fountain listed above were not being used for drinking water.

The water fixtures listed above will be labeled not for drinking until the district’s facilities team can complete remediation and SCI completes retesting. This page will be updated as we make progress remediating fixtures.

See testing result report from SCI.

Return to Safe Water at School.

The Mehlville School District strictly prohibits discrimination and harassment against employees, students or others on the basis of race, color, religion, national origin, age, disability, or sex including pregnancy, sexual orientation, and gender identity and other characteristics protected by law. The following individuals have been designated to handle inquiries regarding the non-discrimination policies: contact Adam Smith at 314-467-5006 or [email protected].